294 • List of all BACnet Properties in Native Operation
Minimum_Off_Time
WAGO-I/O-SYSTEM 750
BACnet/IP Controller
6.45 Minimum_Off_Time
Data Type Unsigned32
Objects Binary output
Description This property, of type Unsigned32, represents the minimum
number of seconds that the Present_Value shall remain in
the INACTIVE state after a write to the Present_Value
property causes that property to assume the INACTIVE
state.
The mechanism used for this is described in the WAGO
BACnet/IP Controller 750-830 Manual in the section "Pri-
oritization".
6.46 Minimum_On_Time
Data Type Unsigned32
Objects Binary output
Description This property, of type Unsigned32, represents the minimum
number of seconds that the Present_Value shall remain in
the ACTIVE state after a write to the Present_Value prop-
erty causes that property to assume the ACTIVE state.
The mechanism used for this is described in the WAGO
BACnet/IP Controller 750-830 Manual in the section "Pri-
oritization".
6.47 Model_Name
Data Type CharacterString
Objects Device
Description This property, of type CharacterString, is assigned by the
vendor to represent the model of the BACnet Device.